The AO845/AO845A Analog Output Module for single or redundant applications has 8 unipolar analog output channels. The module performs self-diagnostic cyclically. Module diagnostics include:
- External Channel Error is reported (only reported on active channels) if the process power supply that supply voltage to output circuitry is too low, or the output current is less than the output set value and the output set value > 1 mA (open circuit).
- Internal Channel Error is reported if the output circuit can not give the right current value. In a redundant pair the module will be commanded to error state by the ModuleBus master.
- Module Error is reported in case of Output Transistor Error, Short Circuit, Checksum Error, Internal Power Supply Error, Status Link Error, Watchdog or Wrong OSP behavior.
Features and benefits
- 8 channels of 4...20 mA
- For single or redundant applications
- 1 group of 8 channels isolated from ground
- Analog inputs are short circuit secured to ZP or +24 V
- HART pass-through communication
General info
Type |
Analog Output |
Signal specification |
4..20mA |
Article number |
3BSE045584R1 |
Number of channels |
8 |
HART |
Yes |
SOE |
No |
Redundancy |
Yes |
High integrity |
No |
Intrinsic safety |
No |
Mechanics |
S800 |
Detailed data
Resolution |
12 bit |
Isolation |
Groupwise isolated from ground |
Under/over range |
±15% |
Output load |
Max 750 Ω |
Error |
Max. 0.1% |
Temperature drift |
Max. 50 ppm/°C |
Rise Time |
Output filter: Disable 23 ms, Enable max 4 mA / 12.5 ms |
Input filter (rise time 0-90%) |
23 ms (0-90%), max 4 mA / 12.5 ms |
Update cycle time |
10 ms |
Current limiting |
Short circuit proof current limited output |
Maximum field cable length |
600 meters (656 yards) |
Rated insulation voltage |
50 V |
Dielectric test voltage |
500 V a.c. |
Power dissipation |
Typ. 3.5 W |
Current consumption +5 V Modulebus |
Max. 125 mA |
Current consumption +24 V external |
218 mA |
Environment and certification
CE mark |
Yes |
Electrical safety |
IEC 61131-2, UL 508 |
Hazardous Location |
C1 Div2 cULus, C1 Zone2 cULus, ATEX Zone 2 |
Marine certification |
BV, DNV-GL, LR |
Protection rating |
IP20 according to IEC 60529 |
Corrosive atmosphere ISA-S71.04 |
G3 |
Climatic operating conditions |
0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
Pollution degree |
Degree 2, IEC 60664-1 |
Mechanical operating conditions |
IEC/EN 61131-2 |
EMC |
EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories |
IEC/EN 60664-1, EN 50178 |
Equipment class |
Class I according to IEC 61140; (earth protected) |
Max ambient temperature |
55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
RoHS compliance |
EN 50581:2012 |
WEEE compliance |
DIRECTIVE/2012/19/EU |